3상
교류(200A)
전류 기록
The PicoLog CM3 Current Data Logger is a compact, easy–to–use data
logger for measuring the power consumption of buildings and machinery.
- 3 channel current data logger
- Suitable for single or three–phase alternating currents
- Low conversion time
- High resolution and accuracy
- No power supply required
- USB and Ethernet interfaces
- Run multiple units on a single PC
High resolution and accuracy
The 24–bit resolution of your PicoLog CM3 ensures that you can detect the
smallest changes in current, while with accuracy within ±1% you know that can
rely on your measurements.
Take measurements at the speed you want
With a conversion time of just 720 ms per channel your PicoLog CM3 is
capable of logging fast changes in current, but we know that in order to
identify problems you may also need to monitor currents over long periods, so
with a PicoLog CM3 you can take measurements at a speed to suit your application
— whether that’s every few seconds, minutes, hours or even every few days.
Monitor currents from your desktop to the other side of the world
With both USB and Ethernet interfaces your PicoLog CM3 can be used in a
variety of situations. If you need a portable instrument that can be used at
various locations and is fast to set up and use, simply connect your laptop to
the PicoLog CM3 by USB. Need to monitor a situation over a period of hours or
days, or from a remote location? Plug your PicoLog CM3 into a spare port on your
network and then access it remotely either from your LAN or over the internet —
thanks to Power over Ethernet (PoE) technology you don’t even need a separate
power supply.
Save Money
Buy a PicoLog CM3 Current Data Logger together with three 200 A current
clamps and not only will you get everything you need to measure three
single–phase currents or all three currents from a three–phase system but you’ll
also save money compared to buying the items separately.
Software that does what you need it to
Your PicoLog CM3 Current Data Logger is supplied with PicoLog data logging
software. With PicoLog you can collect up to one million measurements,
analyse them and then display the results in spreadsheet and graphical formats.
You can view the data both in real–time as you are collecting the measurements,
or you can save the data and view it later. You can also set alarms to warn you
if the current goes above or below a set value.
A software development kit (SDK) is also supplied. The SDK contains a range
of software drivers and example code that you can use to write your own software
or to use your PicoLog CM3 with third–party software such as LabVIEW.
Both PicoLog and the SDK are provided free of charge and updates can be
downloaded for free.
Create your own data acquisition system
With a PicoLog CM3 you can measure three separate currents. If that’s not
enough, using PicoLog software you can add a further 19 PicoLog CM3s to your PC
— enabling you to simultaneously measure up to 60 currents. Alternatively, you
can mix–and–match Pico data loggers to create your own custom data acquisition
system. For example, you may want to monitor how the opening and closing of
doors affects the temperature and electricity usage of a cold room. You could do
this with a PicoLog CM3 and a PT-104.
The only current data logger you need
With three channels, high accuracy and low noise, a PicoLog CM3 Current Data
Logger is ideal for recording data from both single–phase and three–phase AC
supplies. While its compact size, together with having both USB and Ethernet
interfaces, gives you a versatile instrument that you can take with you or leave
on–site for remote monitoring.
Whether you need to monitor three–phase motors and generators, measure the
current consumption of HVAC systems or simply
monitor the current consumed around the home or office, a PicoLog CM3 Current
Data Logger is the only current data logger you need.
Buy your
PicoLog CM3 online or from your local Pico
distributor.
Specifications
| PicoLog CM3 Current Data Logger Specifications |
| Number of chanels |
3 |
| Range (voltage input) |
0 to 1 V AC RMS |
Accuracy (voltage
input) < 200 mV RMS < 1 V RMS |
±1% ±2.5% |
| RMS Noise |
60 µV |
| Resolution |
24 bit |
| Conversion time per enabled
channel |
720 ms |
| Voltage input |
1 V RMS, 20 Hz to 1 kHz |
| Input connectors |
4 mm sockets |
| Input impedance |
>1 MΩ, AC coupled |
| Overvoltage protection |
±30 V DC |
| PC Requirements |
| Minimum |
Processor: Pentium II
processor, or equivalent Memory: 64 MiB (XP) / 512 MiB
(Vista) / 1 GiB (Win 7) Operating system: 32– or 64–bit
edition of Microsoft Windows XP SP2, Vista or Windows
7 Ports: USB 1.1 compliant port or Ethernet |
| Recommended |
Processor: 2 GHz Pentium
IV processor, or equivalent Memory: 256 MiB (XP) / 1 GiB
(Vista / Win 7) Operating system: 32– or 64–bit edition of
Microsoft Windows XP SP2 (or above), Vista or Windows
7 Ports: USB 2.0 compliant port or
Ethernet |
| Environmental |
Operating environment Temperature range Humidity range |
0 °C to 50 °C (20 °C to 28 °C for
stated accuracy) 20% to 80% RH, non–condensing |
Storage environment Temperature range Humidity range |
-20 °C to +60 °C 5% to 95% RH,
non–condensing |
| Physical Properties |
| Dimensions |
184 x 135 x 36 mm (approx 7.2 x 5.3 x 1.4
in) |
| Software |
| PicoLog for Windows |
PicoLog data acquisition software can
collect up to 1 million samples. Features include: Multiple
views — view data as a graph, spreadsheet or text Parameter
scaling — convert raw data into standard engineering
units Math functions — use mathematical equations to
calculate additional parameters Alarm limits — program an
alert if a parameter goes out of a specified range IP
networking — transfer measurements via a LAN or over the Internet Full details on
PicoLog |
| Software development kit |
Includes drivers and example code for
various programming languages including C, C#, Excel and LabVIEW.
|
| Language Support |
Software PicoLog |
Full support for English, French and
German; menus only for Italian, Spanish and Swedish |
Documentation User’s guide Programmer’s guide Installation guide |
English, Français, Deutsch, Italiano,
Español, 中文 English English, Français, Deutsch, Italiano, Español,
Svenska, Nederlandse, Dansk |
| General |
| Data sheet |
English,
中文
(简体), Deutsch,
Español,
Français,
Italiano |
| Additional hardware
(supplied) |
USB 2.0 cable, Ethernet cable, user
manuals, software CD–ROM |
| PC interface |
USB 2.0 (USB 1.1 compatible) or
Ethernet |
| Power requirements |
Powered from USB port or
Ethernet |
| Compliance |
European EMC and LVD standards FCC
Rules Part 15 Class A RoHS
compliant |
| Total Satisfaction
Guarantee |
In the event that this product
does not fully meet your requirements you can return it for an exchange or
refund. To claim, the product must be returned in good condition within 14 days. |
| Warranty |
5 years |
- * US Dollar and Euro prices are approximate.
- Need to know a specification not listed here? - just
ask
페이지 처음으로
|